Model SEWH1500695G

Hight temperature  heat pump for hot water heater

Model SEWH1500695G

ELECTRICAL INPUT
Voltage / Phase380-415 / 3 Phase / 50 Hz
Full Load Amps Per Phase35 Amps
Circuit CB Size50 Amps
RefrigerantR134a
Ambient TempA@ 25°CA@ 8°C
Nominal Heating capacity69.00 KW63.00 KW
Power input13.97 KW14.11 KW
Rating output: 65KW COP:4.65COP:4.89COP:4.46
@setting point : 75°CNoise Level 69 dB @ 3 m
Modbus Protocol RS 485Ambient operation range: -5°C to 45°C
TECHNICAL DATACompressorFan
MakeScroll EmersonEBM
TypeEvi- HighPROPELLER
Number Per Unit22
FLA (Full Load Amps)18.2 Amps3.64Ams(each)
Voltage / Phase415 / 3380-415V/1
Pole/RPM/Air flow m3/hr2 / 2,9006/890/15000
HEAT EXCHANGER/CONTROLER
Water level switch controlControl PanelSmart LCD
Type100% CopperEDWARD
DesignTube in ShellAUSTRALIA
Water Flow Min/Max13m3/h15m3/h
Min/Max. Outlet Water Temp70°C75°C
Design Temperature difference3°K3°K
Design Pressure Drop80 k.P.a80 k.P.a
Max. Operating Pressure2460 k.P.a2460 k.P.a
MATERIALS AND FITTINGS
Water Connections50 mm Copper
Drain20 mm copper
Cabinet ConstructionCold Painted Grey / anti-corrosive coatings
Approx. shipping weight375 kg
Packing Size L x W x H1700 mm x 900 mm x 1765mm
REFWH695G-1500-upload