Model SEAS2000795W

Air source heat pump for hot water heater

Model SEWH2000795G

ELECTRICAL /HEATING
Voltage / Phase380-415 / 3 Phase / 50 Hz
Full Load Amps Per Phase35 Amps
Circuit CB Size55 Amps
RefrigerantR410a
Heating Set Point@A15°C@A35°C
Heating capacity78.10 Kw80.20 Kw
Power input16.62 Kw16.15 Kw
Max output @55°CCOP :4.69COP: 4.97
@setting point : 55°CNoise Level69 dB @ 3 m
Modbus RTU -RS 485Ambient operation range: -5°C to 45°C
MOTION PARTSCompressorFan
MakeScroll EmersonEBM
TypeHermeticPROPELLER
Number Per Unit22
FLA (Full Load Amps)17.9 Amps3.76Ams(each)
Voltage / Phase415 / 3380-415V/1
Pole/RPM/Air flow m3/hr2 / 2,9006/895/16000
HEAT EXCHANGER/CONTROLER
Water level switch controlControl PanelSmart LCD
Type100% CopperTube in Shell
Heat exchanger made byHASEDWARDS- Hanwest Aqua System
Max input/output setting55°C60°C
Water Flow Rate (max/min)@18m3/h@8 m3/h
Water In/Out temp.differ (ΔT)4°K (set point 55°C)5°K (set point 55°C)
Design Pressure Drop80 k.P.a80 k.P.a
Max. Operating Pressure2460 k.P.a2460 k.P.a
MATERIALS AND FITTINGS
Water Connections50 mm Copper
Drain20 mm copper
Cabinet ConstructionPowder coated steel -White
Approx. shipping weight410 kg
Packing Size L x W x H1705 mm x 1008 mm x 1215mm
AS795W